VEX700T Air handling unit

VEX700T

Air handling unit

VEX700T is a perfect rotary air handeling unit for small spaces, due to its small footprint and top connections.
VEX700T
Download CAD Library file
VEX700T
The VEX 700 T is a cost-effective rotary heat exchanger solution that can handle high airflows (up to 10,000 m3/h) despite its small footprint, thanks in part to its top-mounted connections. Its configuration interface enables you to adapt its use to a wide variety of applications.
VEX700T

The + products

  • Air handling units with reduced footprints (vertical fittings, bi-blocks),
  • Siemens Climatix controls,
  • optimal air quality and thermal comfort through a wide range of filter types and coils.
  • Easy to install and configure.

The VEX 700 T brings fresh, filtered air into the building and recovers heat from exhaust air using its high-efficiency heat exchanger. The incoming air can be heated and/or cooled using a comprehensive range of coils.

  • 8 VEX 700 T models up to 10,000 m3/h.,
  • mono & dual-block units,
  • self-supporting construction with galvanised steel panels,
  • external paint finish RAL 7042,
  • insulation with 50 mm of mineral wool, density 70 kg/m³,
  • access to all components via hinged doors fitted to front and to control system via a specific central hatch,
  • high-efficiency rotary heat exchanger (up to 86%),
  • EC motor and high-performance backward curve impeller,
  • compact filters ISO ePM10 50% (M5) on exhaust air and ISO ePM 65 % (F7)

on air supply (as standard),

  • filters available: ISO ePM10 50% (M5), ISO ePM 65% (F7) & ISO ePM1 80% (F9),
  • optional pre-filters: ISO ePM10 50% (M5) or ISO ePM 65% (F7)

External electric, hot water, cold water coils, permutation and evaporator coil +/-,

  • proximity switch available as option,
  • Siemens Climatix control system,
  • de-icing by reducing impeller speed,
  • free-cooling as standard and optional night cooling (with Temp° sensor for room).
  • Siemens Climatix controls:
    • constant speed,
    • constant airflow,
  • constant pressure,
    • airflow control with CO2/VOC sensor (0-10 V signal),
    • built-in clock: operating times can be controlled using a timer.
  • Configuration & monitoring via:
    • remote control,
    • web interface,
    • BMS communication via Modbus RTU, BACnet, TCP/IP or MS/TP protocols.
  • equipment rooms,
  • indoors,
  • vertical duct connection,
  • connects to rectangular fittings (circular connections using transformers),
  • choice of left or right side access.
Available filters Insulation material Connection direction Type of exchanger Type of motor Type of impeller

ISO ePM10 50% (M5), ISO ePM 65% (F7) & ISO ePM1 80% (F9) filters available. ISO ePM10 50% (M5) or ISO ePM 65% (F7) pre-filters as an option.

Top

Counterflow

EC

Backward curve

VEX700T VEX700T
References A (mm) B (mm) C (mm) D (mm) E (mm) F (mm) G (mm) H (mm) K (mm) M (mm) S (mm) Weight (kg)
11069105 - VEX720T

705

740

1630

1010

1245

   

400

200

600

700

250

11069106 - VEX725T

705

740

1630

1010

1245

   

400

200

600

700

250

11069107 - VEX740T

805

840

1630

1110

1345

   

400

250

600

800

280

11069108 - VEX750T

955

1010

1580

1145

1380

690

890

400

350

870

950

340

11069109 - VEX760T

1055

1110

1580

1245

1480

690

890

400

400

870

1050

370

11069110 - VEX770T

1185

1240

1580

1245

1480

690

890

400

450

870

1200

410

11069111 - VEX780T

1405

1460

1930

1405

1680

860

1070

550

500

1050

1300

485

11069112 - VEX790T

1405

1460

1930

1405

1680

860

1070

550

500

1050

1300

500

References Max. airflow (m³/h)
11069105 - VEX720T

800

11069106 - VEX725T

1000

11069107 - VEX740T

1900

11069108 - VEX750T

2900

11069109 - VEX760T

4000

11069110 - VEX770T

5500

11069111 - VEX780T

7500

11069112 - VEX790T

9000

References Max. exchanger output (%)
11069105 - VEX720T

81,1

11069106 - VEX725T

78,6

11069107 - VEX740T

78,4

11069108 - VEX750T

79,7

11069109 - VEX760T

78,8

11069110 - VEX770T

80,9

11069111 - VEX780T

81,1

11069112 - VEX790T

80,8

References Frequency (Hz) Max. current consumption THREE-PHASE 400 V (A) Rated current (A) Max. electrical output of unit (kW) Unit voltage (V)
11069105 - VEX720T    

2

1

400

11069106 - VEX725T

50

2

 

1

400

11069107 - VEX740T

50

3

 

1,5

400

11069108 - VEX750T

50

4,7

 

2,4

400

11069109 - VEX760T

50

7

 

3,5

400

11069110 - VEX770T

50

11,5

 

5,8

400

11069111 - VEX780T

50

13,9

 

7

400

11069112 - VEX790T

50

21,4

 

11

400

  • Text ErP - Ventilation  :  Complies with eco-design regulation 1253/2014 and energy labelling regulation 1254/2014 for ventilation. Energy classes:
  • Eligibility for EEC  :  Yes
  • ESC data sheet no. 1  :  BAT-TH-126

Products and accessories references

  • VEX720T
    VEX720T
    11069105
    from 14097,00 (without VAT)
  • VEX725T
    VEX725T
    11069106
    from 15231,00 (without VAT)
  • VEX740T
    VEX740T
    11069107
    from 17119,00 (without VAT)
  • VEX750T
    VEX750T
    11069108
    from 23156,00 (without VAT)
  • VEX760T
    VEX760T
    11069109
    from 24234,00 (without VAT)
  • VEX770T
    VEX770T
    11069110
    from 25530,00 (without VAT)
  • VEX780T
    VEX780T
    11069111
    from 29304,00 (without VAT)
  • VEX790T
    VEX790T
    11069112
    from 34104,00 (without VAT)

Documents

Showing 1 - y of document
  • ErP sheet VEX700T
    Conformities
    601 KB
  • VEX-DFE Manual of safety
    Manuals
    242 KB
  • VEX700T Installation instructions FR
    Manuals
    5 MB
  • VEX700T Installation instructions EN
    Manuals
    5 MB

1 software