ORDONE smoke exhaust panel

ORDONE smoke exhaust panel

The ORDONE smoke exhaust control panel is addressable and can make major savings on cables.
ORDONE smoke exhaust panel
ORDONE smoke exhaust panel
The ORDONE smoke exhaust control panel is addressable and can make major savings on cables in multi-occupancy residential housing. Using appropriate storey boxes, the number of cables is limited (1 for the 230 V mains power - 1 for the damper remote control - 1 potentially for the damper position control line).
ORDONE smoke exhaust panel

The + products

  • addressable panel: major savings on cables,
  • new: BCE box for exhaust management,
  • new: BNS box for elevator management.
  • MDR module for reliable connection of dampers to storey boxes.

The ORDONE smoke exhaust control panel can locate the source of the alarm and automatically send the smoke and heat exhaust command using appropriate storey boxes.

  • capacity: 16 zones = 16 storeys on 1 bus, or 8 storeys on 2 bus,
  • max. 2 BCE boxes (1 per bus),
  • max. 4 BNS boxes,
  • mains power supply: 230V + 10 %-15 % - 50 Hz,
  • mains consumption: max 12 W,
  • rated voltage: 24 VDC,
  • 2 timed-operation command outputs for smoke and heat exhaust fan,
  • secondary source: 2 x 12V / 7Ah lead batteries, maintenance-free (supplied),
    • battery life: 12 hours on standby following by 1 hour in failsafe mode,
  • fan control: by NO contact 1A 30 VDC, 10-sec timer,
  • report contact: Fire Alarm x 2, Inverter disturbance 1 A 30 VDC,
  • dimensions (mm): Length x Height x Depth = 265 x 482 x 120.
  • BEA storey box:
    • dimensions (mm): L x H x D = 190 x 150 x 90,
    • beyond 3 dampers for 1 BEA, an additional power supply is needed (consult us).

us).

  • MDR modules:
    • serve to avoid any risk of polarity inversion when installing the diodes,
    • pre-wired modules with built-in diode,
    • black MDR = intermediate modules,
    • red MDR = end of line, used for last damper on each storey.
  • BCE exhaust control box:
    • automatically controls the opening of the natural vent in case of failure of the smoke and heat exhaust fan,
    • 24 V safety box output, current make,
    • max. 24 V natural draw damper output, current make,
    • inverter contact on natural draw damper control,
    • dimensions (mm): L x H x D = 190 x 150 x 90.
  • BNS elevator non-stop box:
    • ensures elevator non-stop function,
    • number of contacts = 16 (1 per storey), NO or NC,
    • dimensions (mm): L x H x D = 190 x 150 x 90.
  • install ORDONE smoke exhaust control panel,
  • BEA box:
    • Install on each building storey in the technical duct.
  • BNS box:
    • Install next to elevator machinery.
  • BCE box:
    • Install near to exhaust fan unit.
Insulation material

Products and accessories references

  • ORDONE smoke exhaust panel
    ORDONE smoke exhaust panel
    11044122
    2848,00 (without VAT)
  • BEA storey box
    BEA storey box
    11044123
    272,00 (without VAT)
  • MDR resistor module, black
    MDR resistor module, black
    11044125
    23,80 (without VAT)
  • MDR resistor module red end of line
    MDR resistor module red end of line
    11044126
    23,80 (without VAT)
  • BCE Exhaust control box
    BCE Exhaust control box
    11044127
    579,00 (without VAT)
  • BNS Non-stop elevator box
    BNS Non-stop elevator box
    11044128
    1005,00 (without VAT)

Documents

Showing 1 - y of document
  • Tableau de smoke extraction ORDONE Installation & Maintenance instruction
    Manuals
    3 MB