ProtectONE� TR 2-speed - Independent windings
The + products
- easily adjusted airflow with the exclusive ProtectONE® Adapt system,
- can be fully dismantled as standard (except for insulated model),
- thermal insulation for installation in equipment room,
- backward curve impeller: smaller variation in airflow even if pressure losses vary.
- the backward curve impeller provides better results through slighter changes in the airflow if pressure losses vary.
When commanded by the FACP, the safety box will activate ProtectONE® T in smoke exhaust mode to extract smoke. The box will then switch to “default” mode, then “standby”.
- complies with CE marking 1812-CPR-1548,
- certified EFECTIS F400-120 as per EN12101-3,
- safety box compliant with NF standards (NF S61-937-1, NFS61937-9, NF 537),
- belt-driven exhaust box fan,
- 4 models for airflow from 1,000 to 35,000 m³/h,
- 2-speed motor, independent windings from 1.1 kW to 20 kW,
- balanced backward curve impeller,
- adjustable pulley,
- class F electric motor IP55,
- galvanised steel casing, can be dismantled as standard,
- motor access panel adjustable on site,
- proximity switch fitted in factory,
- airflow adjustment device built into unit: ProtectONE Adapt
(patented system), exclusive to ALDES (option),
-
ProtectONE® TR 2-speed IW can extract:
- smoke and hot gases in case of fire in all non-residential buildings,
- stale air in non-residential and industrial buildings,
- pollutants in professional kitchens.
-
accessories:
- square/circular adjustment plate for intake,
- rain hood anti-bird visor on outlet,
- rectangular and circular flexible sleeve,
- rectangular/circular flexible adapter part on outlet,
- anti-vibration mountings,
- backdraft damper,
- rain hood + grille,
- outlet flange,
- AXONE 1SP safety box, 1-speed progressive start,
- AXONE 2SP safety box, 2-speed smoke exhaust and comfort + smoke exhaust.
-
available options:
- “All-in-One” solution: safety box + switch + pressure switch installed and wired in factory,
- choice of motor access panel,
- horizontal or vertical outlet,
- thermal + acoustic insulation certified 12101-3 for installation in equipment rooms,
- variable pulley,
- ProtectONE® Adapt (patented): rapid airflow adjustment.
- indoors or outdoors,
- indoor installation: use thermal-acoustic insulation option (EN 12101-3),
- outdoor installation: use rain hood + bird screen,
- proximity switch supplied fitted and wired, with position contacts.
Insulation material | Type of motor | Type of impeller |
---|---|---|
AC |
Backward curve |
References | A (mm) | A.R (mm) | B (mm) | B.R (mm) | C (mm) | D (mm) | E (mm) | F (mm) | G (mm) | H (mm) | I (mm) | J (mm) | M (mm) | N (mm) | O (mm) | Weight (kg) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
11039556 - ProtectONE® TR 400 2SP BI | 1608 |
600 |
1213 |
43 |
1141 |
954 |
411 |
145 |
950 |
509 |
431 |
669 |
507 |
507 |
180 |
337 |
11039557 - ProtectONE® TR 450 2SP BI | 1758 |
650 |
1373 |
43 |
1211 |
954 |
561 |
155 |
1000 |
1000 |
485 |
685 |
569 |
569 |
200 |
404 |
11039558 - ProtectONE® TR 500 2SP BI | 1918 |
700 |
1503 |
43 |
1281 |
1034 |
641 |
140 |
1100 |
1100 |
538 |
702 |
638 |
638 |
227 |
435 |
11039559 - ProtectONE® TR 560 2SP BI | 2093 |
800 |
1683 |
43 |
1381 |
1114 |
736 |
140 |
1200 |
1200 |
603 |
737 |
715 |
715 |
248 |
563 |
References | Id/In | Max. current (A) | Rated current (A) | Voltage (V) | Number of poles | Power (kW) |
---|---|---|---|---|---|---|
11039556 - ProtectONE® TR 400 2SP BI | 7.8/7.4-7/4 |
14,85/7,65 |
13,5/6,96-22/8,74 |
400 |
04-june |
6/2,2 - 10/3,3 |
11039557 - ProtectONE® TR 450 2SP BI | 7.8/7.4-7/4 |
14,85/7,65 |
13,5/6,96-22/8,74 |
400 |
04-june |
6/2,2 - 10/3,3 |
11039558 - ProtectONE® TR 500 2SP BI | 7.8/7.4-7/4-8.5/4.5 |
14,85/7,65-32,45/12,32 |
13,5/6,96-22/8,74-29,5/11,2 |
400 |
04-june |
6/2,2 - 10/3,3 - 14/4,5 |
11039559 - ProtectONE® TR 560 2SP BI | 7.8/7.4-7/4-8.5/4.5 |
14,85/7,65-32,45/12,32 |
13,5/6,96-22/8,74-29,5/11,2 |
400 |
04-june |
6/2,2 - 10/3,3 - 14/4,5 |
- PV CE number : 1812-CPR-1548
1 Circular flexible sleeve air intake or outlet
2 Rectangular-circular adapter part for intake
3 Backdraft damper (outlet)
4 Rectangular flexible sleeve (intake + outlet)
5 Outlet flange
6 Flexible rectangular circular adapter part on outlet
7 Rain hood visor and bird screen
8 Anti-vibration mountings
9 Safety box (+ bracket and rain hood visor)
10 Thermal and acoustic insulation
11 Pressure switch
12 Variable pulley
13 ProtectONE® Adapt
14 Vertical outlet grille
Products and accessories references
Documents
-
Certificate of consistency of performance CE - CPR / PV FEU / ProtectONE® TConformities3 MB
-
Extension PV Feu Peinture Epoxy ProtectONEConformities481 KB
-
Declaration of performance (DOP) ProtectONE® TA/TRConformities84 KB
-
EU/EC Declaration of Conformity ProtectONE® TConformities135 KB
-
Conformity CMIM ProtectONE® TConformities36 KB
-
ProtectONE® T Installation & maintenance instructionsManuals3 MB