ProtectONE� R F400 120: 2 Speeds
The + products
- easily adjusted airflow with the exclusive ProtectONE® Adapt system,
- can be fully dismantled as standard (except for insulated model),
- modular connection to discharge: left, right, vertical (except insulated model),
- backward curve impeller: smaller variation in airflow even if pressure losses vary.
- thermal insulation for installation in equipment rooms,
- backward curve impeller provides better results through slighter changes in the airflow if pressure losses vary.
When commanded by the FACP, the safety box will activate ProtectONE® R in smoke exhaust mode to extract smoke. The box will then switch to “default” mode, then “standby”.
- complies with CE marking 1812-CPR-1181,
- certified EFECTIS F400-120 as per EN12101-3,
- Free-wheel fan compliant with ErP 2018,
- airflow from 1000 to 21,000 m³/h,
- class F electric motor IP55,
- 3-phase 2-speed motor,
- built-in airflow adjustment device: ProtectONE® Adapt (patented), exclusive to ALDES (patented),
- centrifugal backward curve impeller coupled directly to motor,
- thermal insulation for installation in equipment room,
- 2 models: in-line output and 90° output.
-
Scope:
- removes smoke and hot gases in case of fire from any commercial building,
- removes contaminated air in commercial and industrial premises,
- removes pollutants in professional kitchens.
-
10 unit sizes for airflow from 1000 to 21,000 m³/h:
- ProtectONE® R2.0 to ProtectONE® R5.0: Size 1,
- ProtectONE® R6.5 to ProtectONE® R9.0: Size 2,
- ProtectONE® R10.0 to ProtectONE® R21.0: Size 3,
- ProtectONE® R2.0 to ProtectONE® R5.0: Size 1 EL,
- ProtectONE® R6.5 to ProtectONE® R9.0: Size 2 EL,
- ProtectONE® R10.0 to ProtectONE® R21.0: Size 3 EL.
-
available options:
- “All-in-One” solution: includes safety box, switch and pressure switch,
- variable pressure switch 100 - 1000 Pa (1 pressure switch for each smoke and heat exhaust speed),
- choice of outlet position: LH/RH access on EL model,
- thermal insulation approved for installation in equipment rooms,
-
accessories:
- square/circular adjustment plate for intake,
- rain hood anti-bird visor on outlet,
- rectangular and circular flexible sleeve,
- anti-vibration mountings,
- backdraft damper.
- indoors or outdoors,
- indoor installation: use thermal-acoustic insulation option (EN 12101-3),
- outdoor installation: use rain hood + bird screen,
- proximity switch supplied fitted and wired, with position contacts.
Insulation material | Type of motor | Type of impeller |
---|---|---|
AC |
Backward curve |
References | A (mm) | B (mm) | C (mm) | D (mm) | H (mm) | I (mm) | L (mm) | Flange (mm) | Insulation (mm) | Weight (kg) |
---|---|---|---|---|---|---|---|---|---|---|
11039281 - ProtectONE® R 4.0 2SP | 300 |
655 |
595 |
595 |
775 |
745 |
660 |
I+20 |
L+50 H+25 |
69 |
11039282 - ProtectONE® R 5.0 2P 1SP | 330 |
655 |
595 |
595 |
775 |
745 |
660 |
I+20 |
L+50 H+25 |
75 |
11039283 - ProtectONE® R 6.5 2SP | 335 |
745 |
695 |
695 |
875 |
835 |
770 |
I+20 |
L+50 H+25 |
102 |
11039284 - ProtectONE® R 8.0 2SP | 335 |
745 |
695 |
695 |
875 |
835 |
770 |
I+20 |
L+50 H+25 |
109 |
11039286 - ProtectONE® R 10.0 2SP | 510 |
905 |
795 |
795 |
1020 |
965 |
910 |
I+20 |
L+50 H+25 |
170 |
11039287 - ProtectONE® R 12.0 2SP | 510 |
905 |
795 |
795 |
1020 |
965 |
910 |
I+20 |
L+50 H+25 |
176 |
11039288 - ProtectONE® R 15.0 2SP | 510 |
905 |
795 |
795 |
1020 |
965 |
910 |
I+20 |
L+50 H+25 |
231 |
11039289 - ProtectONE® R 21.0 2SP | 510 |
905 |
795 |
795 |
1020 |
965 |
910 |
I+20 |
L+50 H+25 |
226 |
11039291 - ProtectONE® R 4.0 EL 2SP | 300 |
595 |
595 |
595 |
775 |
745 |
1070 |
I+20 |
L+50 H+25 |
83 |
11039292 - ProtectONE® R 5.0 2P EL 2SP | 300 |
595 |
595 |
595 |
775 |
745 |
1070 |
I+20 |
L+50 H+25 |
89 |
11039293 - ProtectONE® R 6.5 EL 2SP | 335 |
745 |
695 |
695 |
875 |
835 |
1195 |
I+20 |
L+50 H+25 |
119 |
11039294 - ProtectONE® R 8.0 EL 2SP | 335 |
745 |
695 |
695 |
875 |
835 |
1195 |
I+20 |
L+50 H+25 |
126 |
11039295 - ProtectONE® R9.0 2P EL 2SP | 335 |
745 |
695 |
695 |
875 |
835 |
1195 |
I+20 |
L+50 H+25 |
138 |
11039296 - ProtectONE® R 10.0 EL 2SP | 510 |
795 |
795 |
795 |
1020 |
965 |
1430 |
I+20 |
L+50 H+25 |
193 |
11039297 - ProtectONE® R 12.0 EL 2SP | 510 |
795 |
795 |
795 |
1020 |
965 |
1430 |
I+20 |
L+50 H+25 |
199 |
11039298 - ProtectONE® R 15.0 EL 2SP | 510 |
795 |
795 |
795 |
1020 |
965 |
1430 |
I+20 |
L+50 H+25 |
231 |
11039299 - ProtectONE® R 21.0 EL 2SP | 510 |
795 |
795 |
795 |
1020 |
965 |
1430 |
I+20 |
L+50 H+25 |
249 |
11039285 - ProtectONE® R 9.0 2P 1SP | 335 |
745 |
695 |
695 |
875 |
835 |
770 |
I+20 |
L+50 H+25 |
122 |
References | Id/In | Rated current (A) | Voltage (V) | Number of poles | Power (kW) |
---|---|---|---|---|---|
11039281 - ProtectONE® R 4.0 2SP | 5/3.7 |
1,75/1,05 |
400 |
4/6 |
0,55/0,2 |
11039282 - ProtectONE® R 5.0 2P 1SP | 07/05/2022 00:00:00 |
3,58/1,19 |
400 |
2/4 |
1,5/0,37 |
11039283 - ProtectONE® R 6.5 2SP | 5.5/4.5 |
3,65/1,62 |
400 |
4/6 |
1,5/0,37 |
11039284 - ProtectONE® R 8.0 2SP | 6.5/5 |
4,42/2,33 |
400 |
4/6 |
1,7/0,6 |
11039286 - ProtectONE® R 10.0 2SP | 6/5.5 |
4,91/2,48 |
400 |
4/6 |
2,2/0,7 |
11039287 - ProtectONE® R 12.0 2SP | 7.6/6.2 |
6,85/3,86 |
400 |
4/6 |
3/1 |
11039288 - ProtectONE® R 15.0 2SP | 7.5/7 |
10,2/5,38 |
400 |
4/6 |
4,5/1,5 |
11039289 - ProtectONE® R 21.0 2SP | 7.8/7.4 |
13,7/6,96 |
400 |
4/6 |
6/2,2 |
11039291 - ProtectONE® R 4.0 EL 2SP | 5/3.7 |
1,75/1,05 |
400 |
4/6 |
0,55/0,2 |
11039292 - ProtectONE® R 5.0 2P EL 2SP | 07/05/2022 00:00:00 |
3,58/1,19 |
400 |
02-apr |
1,5/0,37 |
11039293 - ProtectONE® R 6.5 EL 2SP | 5.5/4.5 |
3,65/1,62 |
400 |
04-june |
1,5/0,37 |
11039294 - ProtectONE® R 8.0 EL 2SP | 6.5/5 |
4,42/2,33 |
400 |
04-june |
1,7/0,6 |
11039295 - ProtectONE® R9.0 2P EL 2SP | 7.8/5 |
8,59/2,79 |
400 |
02-apr |
4,4/1,1 |
11039296 - ProtectONE® R 10.0 EL 2SP | 6/5.5 |
4,91/2,48 |
400 |
04-june |
2,2/0,7 |
11039297 - ProtectONE® R 12.0 EL 2SP | 7.6/6.2 |
6,85/3,86 |
400 |
04-june |
03-janv |
11039298 - ProtectONE® R 15.0 EL 2SP | 7.5/7 |
10,2/5,38 |
400 |
04-june |
4,5/1,5 |
11039299 - ProtectONE® R 21.0 EL 2SP | 7.8/7.4 |
13,7/6,96 |
400 |
04-june |
6/2,2 |
11039285 - ProtectONE® R 9.0 2P 1SP | 7.8/5 |
8,59/2,79 |
400 |
2/4 |
4,4/1,1 |
- PV CE number : 1812-CPR-1181
1 Circular flexible sleeve air intake
2 Rectangular-circular adapter part for intake
3 Backdraft damper (outlet)
4 Rectangular flexible sleeve (intake + outlet)
5 Outlet flange
6 Flexible rectangular-circular adapter part on outlet
7 Rain hood and bird screen
8 Anti-vibration mounting
9 Safety box (+ bracket and rain hood visor)
10 Thermal and acoustic insulation
Products and accessories references
Documents
-
Certificate of consistency of performance CE - CPR / PV FEU / ProtectONE® RConformities2 MB
-
Extension PV Feu Peinture Epoxy ProtectONEConformities481 KB
-
Declaration of performance (DOP) ProtectONE® R F400 120Conformities84 KB
-
Conformity CMIM ProtectONE® RConformities37 KB
-
ProtectONE® R Installation & maintenance instructionsManuals6 MB