AXONE Micro III 2-speed/DES - D.PROG: Dual speed smoke and heat exhaust, progressive start-up

AXONE Micro III 2-speed/DES - D.PROG: Dual speed smoke and heat exhaust, progressive start-up

AXONE Micro III 2SP/DES D.PROG is a pre-wired, NF-certified safety box used to control smoke and heat exhaust fans.
AXONE Micro III 2-speed/DES - D.PROG: Dual speed smoke and heat exhaust, progressive start-up
AXONE Micro III 2-speed/DES - D.PROG: Dual speed smoke and heat exhaust, progressive start-up
AXONE Micro III 1SP/DES D.PROG is a pre-wired, NF-certified safety box used to control smoke and heat exhaust fans for non-residential buildings and industrial premises. Connected to the FACP between the main LV distribution board and the fan, it manages any faults with front panel display, stores the last five faults, activates the fan on instruction by the FACP, stops the fan and sets it to standby mode.
AXONE Micro III 1SP/DES provides two fan speeds for smoke and heat exhaust.

When commanded by the FACP, AXONE Micro III 2-speed/DES D/PROG actuates the fan in smoke and heat exhaust mode. When commanded by the fire service shutdown control, it stops the fan and moves to "fault" mode. Then, when the reset command is sent, it moves to "standby" mode.

  • NF certified,
  • IP54 certified by an independent lab,
  • 2 speeds for smoke and heat exhaust only,
  • for 2-speed 3-phase 400 V motor with independent windings (BI), used for power limitation of AES.
  • clear display of state and possible fault on front panel, without opening the box,
  • 2 mini push-buttons inside the box:
    • simulates a Fire service shutdown order,
    • simulates a reset order.
  • insulation check on line “downstream” of box, factory setting 500 k,
  • “upstream” phase check: check phases are present and not inverted,
  • stores condition of box in case of power outage: box resumes initial state on return of power,
  • storage and display of last five faults.
  • new box:
    • clear display of box status and any faults on the front panel, displays last 5 faults,
    • Hinged cover,
    • Smoke exhaust push button control on front panel,
    • Fitted with a progressive starter for high speed mode. Progressive start-up is done automatically.
  • adjust the starter according to the rated motor current in relation to the maximum starter current.
  • Attachment to floor or ground, preferably with flat roof base.
  • For installation outdoors, protect the box against UV radiation using the flat roof base.
  • The AXONE Micro III flat roof base is made of galvanised steel and is equipped with a protective rain and UV cover. It serves to attach the safety box to the floor for a tidy installation.
  • If the base is fixed against a wall, use the appropriate wall attachment brackets.
Size

T2

AXONE Micro III 2-speed/DES - D.PROG: Dual speed smoke and heat exhaust, progressive start-up
H (mm) L (mm) P (mm)

400

500

210

References Rated current (A)
11090711 - Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 16.7A

16,7

11090712 - Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 25.4A

25,4

11090713 - Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 43.3A

43,3

11090714 - Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 60A

60

Products and accessories references

  • Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 16.7A
    Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 16.7A
    11090711
    6559,62 (without VAT)
  • Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 25.4A
    Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 25.4A
    11090712
    7354,20 (without VAT)
  • Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 43.3A
    Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 43.3A
    11090713
    9980,70 (without VAT)
  • Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 60A
    Axone Micro III 2-speed / Smoke exhaust - Independent windings - Prog st 60A
    11090714
    10664,10 (without VAT)

Documents

Showing 1 - y of document
  • Installation instructions - general - AXONE Micro III
    Manuals
    243 KB
  • Installation instructions AXONE Micro III 2 Speed smoke extraction -BI Soft start 16,7/25,4/43,3/60 A
    Manuals
    279 KB