AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust

AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust

AXONE Micro III 2SP/CONF is a pre-wired, NF-certified safety box used to control smoke and heat exhaust fans.
AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust
AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust
AXONE Micro III 2SP/CONF is an NF-certified safety box used to control smoke and heat exhaust fans in non-residential buildings and industrial premises. Connected to the FACP between the main LV distribution board and the fan, it manages any faults with front panel display, stores the last five faults, activates the fan on instruction by the FACP, stops the fan and sets it to comfort mode.
AXONE Micro III 2-SP/CONF offers one smoke and heat exhaust speed (high speed) with low and high-speed comfort control.
AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust

The + products

  • version with built-in switch and pressure switch: ideal for box installed at less than 2 m from fan,
  • easy wiring,
  • diagnostic assistance,
  • Stores and displays the last 5 faults.

When instructed by the FACP, AXONE Micro III 2SP/CONF activates the fan in "smoke and heat exhaust" mode. When instructed by the Fire service shutdown control, it stops the fan and sets it to “default” mode. Then, using the reset control, it changes to “standby” mode.

  • NF certified,
  • IP54 certified by an independent lab,
  • for 2-speed 3-phase 400 V motor with independent windings (BI) and Dahlander coupling (DAH),
  • use a BI safety box for a “1-speed” fan operating in comfort and smoke and heat exhaust modes,
  • high speed smoke and heat exhaust, comfort mode low speed and high speed,
  • 2 versions:
    • basic unit,
    • unit with p and 2 pressure switches built in (IPDP) at 16.7A,
  • insulation check on line “downstream” of box, factory setting 500 k,
  • “upstream” phase check: check phases are present and not inverted,
  • stores condition of box in case of power outage: box resumes initial state on return of power,
  • storage and display of last five faults.
  • Clear display of box status and any faults on front panel,
  • hinged cover,
  • smoke and heat exhaust push button on front panel,
  • 2 versions:
    • basic box,
    • unit with proximity switch and built-in pressure switch (IPDP) at 4.7A and 16.7A
  • 2 push buttons inside box to perform a full cycle:
    • simulates a Fire service shutdown order,
    • simulates a reset order,
  • Stores and displays the last 5 faults.
  • Install the safety box either close to the LV distribution panel or close to the fan unit.
  • attach the box to the floor or the wall, preferably using the recommended flat roof base,
  • outdoors, use the flat roof base,
  • use the wall attachment brackets if the flat roof base is attached to a wall.
References Size
11090700 - Axone Micro III 2-speed/Comfort - Dahlander winding - 16.7A

T2

11090701 - Axone Micro III 2-speed/Comfort - Dahlander winding - 25.4A

T2

11090702 - Axone Micro III 2-speed/Comfort - Dahlander winding - 43.3A

T2

11090699 - Axone Micro III 2-speed/Comfort - Dahlander winding - 100A

T0+T2

11090703 - Axone Micro III 2-speed/Comfort - Dahlander winding - 63.3A

T0+T2

11090704 - Axone Micro III 2-Speed/Comfort - Dahlander -16.7A+Prox switch+Pres switch

T2

11090705 - Axone Micro III 2-speed/Comfort - Independent winding - 16.7A

T1

11090706 - Axone Micro III 2-speed/Comfort - Independent winding - 25.4A

T2

11090707 - Axone Micro III 2-speed/Comfort - Independent winding - 43.3A

T2

11090708 - Axone Micro III 2-speed/Comfort - Independent winding - 63.3A

T2

11090709 - Axone Micro III 2-Speed/Comfort - Ind. wind. -16.7A+Prox switch+Pres switch

T1

AXONE Micro III 2SP/CONF: Two speeds "Comfort + smoke and heat exhaust
References H (mm) L (mm) P (mm)
11090700 - Axone Micro III 2-speed/Comfort - Dahlander winding - 16.7A

500

400

210

11090701 - Axone Micro III 2-speed/Comfort - Dahlander winding - 25.4A

500

400

210

11090702 - Axone Micro III 2-speed/Comfort - Dahlander winding - 43.3A

500

400

210

11090699 - Axone Micro III 2-speed/Comfort - Dahlander winding - 100A

700

500

300

11090703 - Axone Micro III 2-speed/Comfort - Dahlander winding - 63.3A

700

500

300

11090704 - Axone Micro III 2-Speed/Comfort - Dahlander -16.7A+Prox switch+Pres switch

400

560

210

11090705 - Axone Micro III 2-speed/Comfort - Independent winding - 16.7A

400

300

150

11090706 - Axone Micro III 2-speed/Comfort - Independent winding - 25.4A

500

400

210

11090707 - Axone Micro III 2-speed/Comfort - Independent winding - 43.3A

500

400

210

11090708 - Axone Micro III 2-speed/Comfort - Independent winding - 63.3A

500

400

210

11090709 - Axone Micro III 2-Speed/Comfort - Ind. wind. -16.7A+Prox switch+Pres switch

400

360

150

References Rated current (A)
11090700 - Axone Micro III 2-speed/Comfort - Dahlander winding - 16.7A

16,7

11090701 - Axone Micro III 2-speed/Comfort - Dahlander winding - 25.4A

25,4

11090702 - Axone Micro III 2-speed/Comfort - Dahlander winding - 43.3A

43,3

11090699 - Axone Micro III 2-speed/Comfort - Dahlander winding - 100A

100

11090703 - Axone Micro III 2-speed/Comfort - Dahlander winding - 63.3A

63,3

11090704 - Axone Micro III 2-Speed/Comfort - Dahlander -16.7A+Prox switch+Pres switch

16,7

11090705 - Axone Micro III 2-speed/Comfort - Independent winding - 16.7A

16,7

11090706 - Axone Micro III 2-speed/Comfort - Independent winding - 25.4A

25,4

11090707 - Axone Micro III 2-speed/Comfort - Independent winding - 43.3A

43,3

11090708 - Axone Micro III 2-speed/Comfort - Independent winding - 63.3A

63,3

11090709 - Axone Micro III 2-Speed/Comfort - Ind. wind. -16.7A+Prox switch+Pres switch

16,7

Products and accessories references

  • Axone Micro III 2-speed/Comfort - Dahlander winding - 16.7A
    Axone Micro III 2-speed/Comfort - Dahlander winding - 16.7A
    11090700
    2748,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Dahlander winding - 25.4A
    Axone Micro III 2-speed/Comfort - Dahlander winding - 25.4A
    11090701
    3785,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Dahlander winding - 43.3A
    Axone Micro III 2-speed/Comfort - Dahlander winding - 43.3A
    11090702
    5109,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Dahlander winding - 100A
    Axone Micro III 2-speed/Comfort - Dahlander winding - 100A
    11090699
    6541,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Dahlander winding - 63.3A
    Axone Micro III 2-speed/Comfort - Dahlander winding - 63.3A
    11090703
    6541,00 (without VAT)
  • Axone Micro III 2-Speed/Comfort - Dahlander -16.7A+Prox switch+Pres switch
    Axone Micro III 2-Speed/Comfort - Dahlander -16.7A+Prox switch+Pres switch
    11090704
    2967,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Independent winding - 16.7A
    Axone Micro III 2-speed/Comfort - Independent winding - 16.7A
    11090705
    2325,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Independent winding - 25.4A
    Axone Micro III 2-speed/Comfort - Independent winding - 25.4A
    11090706
    2955,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Independent winding - 43.3A
    Axone Micro III 2-speed/Comfort - Independent winding - 43.3A
    11090707
    3921,00 (without VAT)
  • Axone Micro III 2-speed/Comfort - Independent winding - 63.3A
    Axone Micro III 2-speed/Comfort - Independent winding - 63.3A
    11090708
    4663,00 (without VAT)
  • Axone Micro III 2-Speed/Comfort - Ind. wind. -16.7A+Prox switch+Pres switch
    Axone Micro III 2-Speed/Comfort - Ind. wind. -16.7A+Prox switch+Pres switch
    11090709
    2535,00 (without VAT)

Documents

Showing 1 - y of document
  • Installation instructions - general - AXONE Micro III
    Manuals
    243 KB
  • Installation instructions AXONE Micro III 2V/CONF : 2 Speeds "Confort + smoke extraction DAHLANDER 16,7/25,4/43,3/63,3/100 A
    Manuals
    225 KB