AXONE Micro III 2SP/CONF: Two speeds smoke and heat exhaust

AXONE Micro III 2SP/CONF: Two speeds smoke and heat exhaust

AXONE Micro III 2SP/DES is a pre-wired, NF-certified safety box used to control smoke and heat exhaust fans.
AXONE Micro III 2SP/CONF: Two speeds smoke and heat exhaust
AXONE Micro III 2SP/CONF: Two speeds smoke and heat exhaust
AXONE Micro III 2SP/DES is a pre-wired NF-certified safety box used to control smoke and heat exhaust fans in non-residential buildings and industrial premises. Connected to the FACP between the main LV distribution board and the fan, it manages any faults with front panel display, stores the last five faults, activates the fan on instruction by the FACP, stops the fan and sets it to standby mode.
AXONE Micro III 1SP/DES provides two fan speeds for smoke and heat exhaust.
AXONE Micro III 2SP/CONF: Two speeds smoke and heat exhaust

The + products

  • version with built-in switch and pressure switch: ideal for box installed at less than 2 m from fan,
  • easy wiring,
  • diagnostic assistance display,
  • Stores and displays the last 5 faults.

When instructed by the FACP, AXONE Micro III 2SP/DES activates the fan in smoke and heat exhaust mode. When instructed by the Fire service shutdown control, it stops the fan and sets it to “default” mode. Then, using the reset control, it changes to “standby” mode.

  • NF certified,
  • IP54 certified by an independent lab,
  • 2 speeds for smoke and heat exhaust only,
  • for 2-speed 3-Ph 400 V motor with independent windings (BI) and Dahlander coupling (DAH),
  • 2 versions:
    • basic unit,
    • unit with p and 2 pressure switches built in (IPDP) at 16.7A,
  • clear display of state and possible fault on front panel, without opening the box,
  • 2 speed control buttons (high / low) on front panel,
  • 2 mini push-buttons inside the box:
    • simulates a Fire service shutdown order,
    • simulates a reset order.
  • insulation check on line “downstream” of box, factory setting 500 k,
  • “upstream” phase check: check phases are present and not inverted,
  • stores condition of box in case of power outage: box resumes initial state on return of power,

stores and displays the last five faults.

  • specific aspects compared to 1-speed motor:
    • two power lines from AXONE Micro to the motor: BPV and BGV,
    • two lines from the FACP to command smoke and heat exhaust mode at low speed or high speed: JPV and JGV,
    • an extra pressure sensor to ensure a safety position for each speed setting: MPV and MGV,
    • an extra independent fault summary to provide "standby" information for each speed setting: NPV and NGV.
  • stores and displays the last 5 faults,
  • Install the safety box either close to the LV distribution panel or close to the fan unit.
  • attach the box to the floor or the wall, preferably using the recommended flat roof base,
  • outdoors, use the flat roof base,
  • use the wall attachment brackets if the flat roof base is attached to a wall.

Products and accessories references

Documents

Showing 1 - y of document
  • Installation instructions - general - AXONE Micro III
    Manuals
    243 KB
  • Installation instructions AXONE Micro III 2V/DES : 2 Speeds smoke extraction Independent windings smoke extraction only 16,7/25,4/43,3/63,3/100 A
    Manuals
    278 KB
  • Installation instructions AXONE Micro III 2V/DES : 2 Speeds smoke extraction DAHLANDER smoke extraction Seul 16,7/25,4/43,3/63,3/100 A
    Manuals
    277 KB