VEX700T
Air handling unit
VEX700T
Air handling unit
VEX700T is a perfect rotary air handeling unit for small spaces, due to its small footprint and top connections.
VEX700T
The VEX 700 T is a cost-effective rotary heat exchanger solution that can handle high airflows (up to 10,000 m3/h) despite its small footprint, thanks in part to its top-mounted connections. Its configuration interface enables you to adapt its use to a wide variety of applications.
The + products
- Air handling units with reduced footprints (vertical fittings, bi-blocks),
- Siemens Climatix controls,
- optimal air quality and thermal comfort through a wide range of filter types and coils.
- Easy to install and configure.
The VEX 700 T brings fresh, filtered air into the building and recovers heat from exhaust air using its high-efficiency heat exchanger. The incoming air can be heated and/or cooled using a comprehensive range of coils.
- 8 VEX 700 T models up to 10,000 m3/h.,
- mono & dual-block units,
- self-supporting construction with galvanised steel panels,
- external paint finish RAL 7042,
- insulation with 50 mm of mineral wool, density 70 kg/m³,
- access to all components via hinged doors fitted to front and to control system via a specific central hatch,
- high-efficiency rotary heat exchanger (up to 86%),
- EC motor and high-performance backward curve impeller,
- compact filters ISO ePM10 50% (M5) on exhaust air and ISO ePM 65 % (F7)
on air supply (as standard),
- filters available: ISO ePM10 50% (M5), ISO ePM 65% (F7) & ISO ePM1 80% (F9),
- optional pre-filters: ISO ePM10 50% (M5) or ISO ePM 65% (F7)
External electric, hot water, cold water coils, permutation and evaporator coil +/-,
- proximity switch available as option,
- Siemens Climatix control system,
- de-icing by reducing impeller speed,
- free-cooling as standard and optional night cooling (with Temp° sensor for room).
-
Siemens Climatix controls:
- constant speed,
- constant airflow,
-
constant pressure,
- airflow control with CO2/VOC sensor (0-10 V signal),
- built-in clock: operating times can be controlled using a timer.
-
Configuration & monitoring via:
- remote control,
- web interface,
- BMS communication via Modbus RTU, BACnet, TCP/IP or MS/TP protocols.
- equipment rooms,
- indoors,
- vertical duct connection,
- connects to rectangular fittings (circular connections using transformers),
- choice of left or right side access.
- Text ErP - Ventilation : Complies with eco-design regulation 1253/2014 and energy labelling regulation 1254/2014 for ventilation. Energy classes:
- Eligibility for EEC : Yes
- ESC data sheet no. 1 : BAT-TH-126