OPTONE�-H "+ Grille
Volet de désenfumage
OPTONE�-H "+ Grille
Volet de désenfumage
The OPTONE-H "+ Grille” damper is used for smoke and heat exhaust on ducting in residential buildings in categories 3B or 4.
OPTONE�-H "+ Grille
The OPTONE-H "+ Grille” damper is used for smoke and heat exhaust on ducting in residential buildings in categories 3B or 4. It is ideal for installation in a standard 400x500 mm duct (20 dm²). The OPTONE-H "+ Grille” damper features a 24V current-make trigger mechanism. However it is not fitted with signal contacts and is unable to receive them.
The + products
- metal trim, aesthetic and vandal-proof,
- shallow articulation range,
- simplified cable inputs and outputs.
- aesthetic grille with removable core,
- national stock for short delivery times,
- individually packed,
- aesthetic electrical protective trim.
The damper is closed in standby position. It opens when instructed by the ORDONE control panel, then moves into safety position.
- CE marking compliant as per EN 12101-8.
- free air passage of 20.3 dm2,
- first smoke control damper certified EI 60 S compliant with European standard NF EN 1366-10,
- identical damper for smoke and heat exhaust (VH) and air inlet (VB),
- 1-hour fire resistant in accordance with decision of 31 January 1986. Ideal for installation on standard duct 400 x 500 mm,
- electromagnetic trip device VDS 24 V DC auto-reset,
- mounting frame can be installed in factory,
- cable through holes included,
- grille with removable core,
- connection terminal block: protected by a plastic cover,
- individually packed,
- for a damper fitted with signalling contacts, use the OPTONE T damper range.
-
mounting frame:
- galvanised steel 20/10 mm,
- suited for installation on concrete and on lightweight materials such as Promatect, Supalux
or Tecniver,
-
- drilled to enable passage of electric cables,
- fitted with sealing lugs and holes to receive damper screws.
- top/down reversible,
- 70 mm depth for good mechanical strength.
- installation direction: “fire in the duct”,
- surface-mounted on a smoke and heat exhaust duct CF 1h fire rating
- attachment of OPTONE-H "+ Grille" on mounting frame recommended,
-
install the OPTONE-H "+ Grille” with the clips at the top to installed the fin core:
- at the bottom for a VB damper,
- at the top for a VH damper.
- for installation with mortar-sealed mounting frame on concrete duct, add at least 100 mm for mortar,
- for other dimensions use the OPTONE range.
References | Free air passage section (dm²) | Free air passage section (mm x mm) | Insulation material |
---|---|---|---|
11044000 - OPTONE®-H + Grille 1/1-flap - VDS24 - 400x650 | 20,3 |
343 x 593 |
|
11044003 - OPTONE®-H Classic 1/1F-VDS 24 - 400X650 | 20 |
References | L x H (mm) | S (dm²) | Flap penetrating side (excluding frame) (mm) | Grille overall - flap overall (mm) | Minimum duct depth (mm) | Opening with mounting frame (without sealing) (mm) |
---|---|---|---|---|---|---|
11044000 - OPTONE®-H + Grille 1/1-flap - VDS24 - 400x650 | 400 x 650 |
483 x 633 |
443 x 693 |
425 |
400 x 650 |
|
11044003 - OPTONE®-H Classic 1/1F-VDS 24 - 400X650 | 400 x 650 |
20 |
Products and accessories references
Documents
Showing 1 - y of
document
-
Certificate of consistency of performance CE - CPR / PV FEU / OPTONE® "+GrilleConformities2 MB
-
Laboratory assessment OPTONE on concrete ductConformities700 KB
-
Declaration of performance (DOP) OPTONE® "+ GrilleConformities224 KB
-
Fire resistance rating certificate OPTONE® "+Grille" 1VConformities2 MB
-
OPTONE®-H Installation & maintenance instructionsManuals1 MB